Use voc sensors to monitor voc in the air

Use voc sensors to monitor voc in the air
JXCTTime:2023-2-14

voc sensors

There are two ways to monitor voc:

  1. The use of an onsite PID meter (photo-ionizing detector) for real-time total VOC levels (tVOCs)
  2. The use of sorbent tubes or air-capturing devices for lab analysis (usually GCMS) or summa canisters and regulators to target a wide variety of compounds by EPA method TO-15.

VOC Sensor Capabilities

A VOC sensors informed ventilation system can optimize indoor air quality while minimizing energy use. There are over 5,000 VOCs that are expelled by breathing, cooking, bodily functions, perfumes, deodorants, paint, cleaners, cigarettes, office supplies, etc.

JXCT’s VOC sensor monitors these gases and provides a CO2 equivalent ppm (parts per million) output which is then input to a DCV system.

voc sensorsThe VOC sensors eliminates the need for frequent manual calibration by providing a relative measurement and using an ABC logic algorithm. With ABC self-correction, the sensor constantly adjusts the 450 ppm baseline  to eliminate any sensor drift. The logic drives the sensor to quickly reduce the baseline when a time of low measurement is sensed.

The voc sensor directly measures ambient concentrations of a broad range of “reducing gases” associated with bad air quality. Examples are: alcohols, aldehydes, ketones, organic acids, amines, organic chloramines, aliphatic and aromatic hydrocarbons. These gases all burn and cause the VOC sensor ppm output to increase. Opposite examples are sulfuric acid, nitric acid and ozone. These three are “oxidizing gases” (rather than “reducing gases”) and will NOT cause the VOC sensor ppm output to increase. OSHA has set an exposure limit for sulfuric acid of 1 mg/m3 TWA (time weighted average).

However, a VOC sensor is not the appropriate tool to monitor sulfuric acid or any other “oxidizing gases”.

VOC Sensor Limitations

voc sensors

Because of the relative nature of the sensor output, the VOC sensors cannot define an accuracy tolerance. By definition, accuracy is the variation from an absolute measurement. Since the VOC sensor uses ABC logic, there is no absolute measurement.

The VOC sensor is not an analytical instrument and should not be used in a safety application. It is a broad range sensor that cannot break out measurements of individual gases. For example, OSHA has set permissible exposure limits for ethyl alcohol. The VOC sensor will show elevated levels when ethyl alcohol is present and signal the HVAC system to increase ventilation, but the sensor cannot provide a specific ppm measurement of ethyl alcohol so that the user can document compliance to OSHA exposure limits.

The VOC sensor was designed to monitor common indoor air quality contaminants only. There are several gases that will affect the sensor reading but are not typical indoor contaminants. Typical outdoor gases such as SO2, H2, and CO will affect the sensor but have not been tested. The VOC sensor should not be used to monitor CO as it is not sensitive enough to meet safety and OSHA requirements.

The BAPI VOC sensor provides a CO2 equivalent ppm output so that Ashrae’s popular CO2-based VRP procedure can be used for DCV; however, CO2 is not one of the VOCs that the sensor monitors. If your application needs to directly measure CO2, choose a CO2 sensor.